Siemens TeleControl Server Basic: Remote Auth Bypass

🔒 Siemens TeleControl Server Basic V3.1 contains a critical missing-authentication vulnerability (CVE-2025-40765) that allows unauthenticated remote attackers to obtain user password hashes and perform authenticated database operations. The issue carries a CVSS v3.1 score of 9.8 and a CVSS v4 score of 9.3, with network attack vector and low attack complexity. Siemens advises updating to V3.1.2.3 or later and restricting access to port 8000; CISA emphasizes isolating control networks and minimizing internet exposure. Tenable reported the issue and, to date, CISA has not received reports of public exploitation.
read more →

SINEC NMS SQL Injection (CVE-2025-40755) — Siemens Advisory

🛡️ This advisory details an SQL injection vulnerability in Siemens SINEC NMS (versions prior to V4.0 SP1) affecting the getTotalAndFilterCounts endpoint. Assigned CVE-2025-40755 with high severity (CVSS v3.1 8.8 / CVSS v4 8.7), an authenticated low-privilege attacker could inject SQL to insert data and escalate privileges. Siemens advises updating to V4.0 SP1 or later and applying network protections such as segmentation and firewalls; CISA reports no known public exploitation.
read more →

Rockwell FactoryTalk Linx MSI Privilege Chaining Flaw

⚠️ Rockwell Automation disclosed two privilege-chaining vulnerabilities in FactoryTalk Linx (versions 6.40 and prior) that allow authenticated Windows users to escalate to SYSTEM privileges by hijacking MSI repair console windows. The issues are tracked as CVE-2025-9067 and CVE-2025-9068 and carry a CVSS v4 base score of 8.5 (CVSS v3.1 7.8). Rockwell recommends applying the Microsoft MSI patch and upgrading to FactoryTalk Linx 6.50 or later; CISA notes these flaws are not remotely exploitable and no public exploitation has been reported.
read more →

Rockwell FactoryTalk ViewPoint XML External Entity Flaw

🔒 Rockwell Automation reported a FactoryTalk ViewPoint XML External Entity (XXE) vulnerability (CVE-2025-9066) that can be exploited remotely with low attack complexity to induce a temporary denial-of-service via crafted SOAP requests. Affected devices include PanelView Plus 7 terminals (version 14 and prior). Rockwell released firmware fixes and patches, and CISA recommends minimizing network exposure, isolating control networks, and applying vendor updates promptly. The vulnerability is scored CVSS v4 8.7 (CVSS v3.1 7.5).
read more →

Rockwell Automation PanelView and FactoryTalk ME Flaws

🔒 Rockwell Automation disclosed vulnerabilities in FactoryTalk View Machine Edition and PanelView Plus 7 that can allow unauthorized access to device file systems and diagnostic data. CVE-2025-9064 is a network-exploitable path traversal issue; CVE-2025-9063 is an improper-authorization flaw tied to an ActiveX control. Rockwell recommends installing provided firmware and software updates, and CISA advises minimizing network exposure, isolating control networks, and using secure remote access.
read more →

CISA Publishes Four ICS Advisories on October 9, 2025

🔔 CISA released four Industrial Control Systems (ICS) Advisories on October 9, 2025, covering vulnerabilities in Hitachi Energy Asset Suite, Rockwell Automation Lifecycle Services with Cisco, Rockwell Automation Stratix, and an update to Mitsubishi Electric Multiple FA Products. Each advisory provides technical details, risk ratings, and recommended mitigations. Administrators and asset owners should review the advisories promptly and apply mitigations or vendor patches to reduce exposure. CISA emphasizes timely review and implementation to protect operational environments.
read more →

Delta DIAScreen Multiple Out-of-Bounds Write Flaws

⚠️ Delta Electronics issued an advisory for DIAScreen addressing four out-of-bounds write vulnerabilities (CWE-787) that can be triggered when a valid user opens a maliciously crafted project file. The issues are tracked as CVE-2025-59297 through CVE-2025-59300 and have CVSS v3.1 base scores of 6.6 and CVSS v4 base scores of 6.8. Delta released v1.6.1 to remediate the flaws; administrators should apply the update and follow CISA guidance on social-engineering protections and ICS defensive best practices.
read more →

CISA Issues Two New ICS Advisories for Delta, Rockwell

🛡️ CISA released two Industrial Control Systems advisories on October 7, 2025, addressing security issues in Delta Electronics DIAScreen and an updated advisory for Rockwell Automation 1756-EN4TR/1756-EN4TRXT. The notices provide technical details, vulnerability descriptions, and recommended mitigations to reduce exposure in operational environments. Administrators and users are urged to review the advisories and apply mitigations promptly to protect ICS assets.
read more →

Raise3D Pro2 Series Authentication Bypass Advisory

⚠️ CISA warns of a high-severity authentication bypass in Raise3D Pro2 Series 3D printers caused by an unauthenticated debug port that can expose the device file system. The flaw, CVE-2025-10653, has a CVSS v4 score of 8.8 and is remotely exploitable with low complexity when developer mode is enabled. Raise3D is developing firmware fixes; users should disable developer mode and limit network access until patched.
read more →

CISA Issues Two ICS Advisories for Raise3D and Hitachi Energy

🔔 CISA released two Industrial Control Systems advisories on October 2, 2025, covering Raise3D Pro2 Series 3D printers (ICSA-25-275-01) and the Hitachi Energy MSM product (ICSA-25-275-02). Each advisory provides technical details on reported vulnerabilities, potential impacts to device confidentiality, integrity, or availability, and recommended mitigations including configuration changes and firmware updates where available. CISA encourages operators and administrators to review the advisories promptly, implement vendor recommendations, and apply compensating controls to reduce operational risk.
read more →

OpenPLC_V3 Denial-of-Service Vulnerability (CVE-2025-54811)

⚠️ CISA published an advisory for OpenPLC_V3 describing a denial-of-service vulnerability (CVE-2025-54811) caused by a missing return in the enipThread function that can trigger an illegal instruction and crash the PLC runtime. The flaw affects versions prior to pull request #292 and can stop PLCs under certain conditions. A patch is available in PR #292; administrators should update and isolate affected devices.
read more →

Festo CECC Controller Firmware Vulnerabilities and Fixes

⚠️ Festo firmware for Controller CECC-S, -LK, and -D families contains multiple vulnerabilities (aggregate CVSS up to 9.8) in the integrated CODESYS V3 runtime and related components. Affected releases include R05 (2.3.8.0) and R06 (2.3.8.1); Festo advises updating affected units to firmware 2.4.2.0 where fixes are provided. Exploitable issues may enable remote code execution, denial-of-service, privilege escalation, or unauthorized access. CISA recommends isolating control networks, restricting remote exposure, and applying vendor guidance and mitigations while performing appropriate risk analysis.
read more →

CISA Publishes Ten New ICS Advisories — Sept 30, 2025

🔔 On September 30, 2025, CISA released ten Industrial Control Systems advisories summarizing current security issues, vulnerabilities, and known exploits affecting a range of ICS products. The advisories cover MegaSys Enterprises, multiple Festo devices, OpenPLC_V3, National Instruments Circuit Design Suite, LG Innotek cameras, and updates for Keysight Ixia, HEIDENHAIN, and Rockwell Automation. Administrators are urged to review the technical details and apply recommended mitigations promptly to reduce operational risk.
read more →

Festo CPX-CEC-C1 and CPX-CMXX Privilege Flaw — Remote

⚠️ Festo CPX-CEC-C1 and CPX-CMXX devices contain an improper privilege management vulnerability (CWE-269) that permits unauthenticated remote access to critical webserver functions and may cause a denial of service. The issue is identified as CVE-2022-3079 with a CVSS v3.1 base score of 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/A:H). Festo currently has no firmware fix planned; recommended mitigations include restricting access to TCP port 80 and replacing affected units with specified follow-up products.
read more →

Seven Nations Publish Unified OT Security Guidance

🛡️ National cybersecurity agencies from seven countries released unified operational technology (OT) security guidance on 29 September, aimed at practitioners who deploy or operate OT equipment and systems. The document is organised around five core principles and supplies step-by-step actions for OT security teams to strengthen resilience. It emphasises creating and maintaining a definitive record that covers asset classification, connectivity mapping, system architecture and third-party risks.
read more →

CISA and NCSC Joint Guidance on Securing OT Systems

🔒 CISA, the FBI, the UK NCSC, and international partners published joint guidance titled Creating and Maintaining a Definitive View of Your Operational Technology (OT) Architecture. The guidance explains how organizations can use data sources such as asset inventories and manufacturer-provided resources, including software bill of materials, to create and maintain an accurate OT record. It highlights benefits like improved risk assessment, prioritization of critical and exposed systems, and stronger architectural controls, and recommends cross-team collaboration and alignment with IEC 62443 and ISO/IEC 27001.
read more →

CISA Releases One Industrial Control Systems Advisory

🔔 CISA released one Industrial Control Systems advisory on September 25, 2025 addressing Dingtian DT-R002. The advisory, ICSA-25-268-01, provides technical details on identified vulnerabilities and recommended mitigations for affected ICS devices. Administrators and operators are encouraged to review the advisory promptly and apply mitigations to reduce operational risk. This product is provided subject to CISA's Notification and Privacy & Use policies.
read more →

Dingtian DT-R002 Relay Board: Credentials Disclosure Risk

⚠️ CISA warns that the Dingtian DT-R002 relay board contains two Insufficiently Protected Credentials vulnerabilities (CVE-2025-10879, CVE-2025-10880) that allow unauthenticated attackers to retrieve a username and extract the proprietary protocol password. Both flaws affect all versions, are remotely exploitable with low complexity, and carry CVSS v4 base scores of 8.7. Dingtian has not engaged with CISA; users should restrict HTTP (TCP/80) and the Dingtian protocol on UDP/60000–60001, isolate devices from the internet, and follow ICS defensive best practices.
read more →

CISA Issues Six New Industrial Control Systems Advisories

🔔 CISA released six Industrial Control Systems (ICS) advisories on September 23, 2025, providing timely information on security issues, vulnerabilities, and potential exploits across multiple product families. The advisories cover AutomationDirect CLICK PLUS, Mitsubishi Electric MELSEC‑Q Series CPU Module, Schneider Electric SESU, Viessmann Vitogate 300, and two updates for Hitachi Energy RTU500 Series. Users and administrators are urged to review each advisory for technical details and apply recommended mitigations promptly.
read more →

Viessmann Vitogate 300: OS Command Injection Risks

🚨 CISA published an advisory on September 23, 2025, describing high‑severity vulnerabilities in Viessmann's Vitogate 300 gateway. The advisory identifies an OS command injection (CWE‑78, CVE‑2025‑9494) and a client‑side enforcement bypass (CWE‑602, CVE‑2025‑9495) that can enable command modification or unexpected client–server interactions. A CVSS v4 base score of 8.7 is reported overall, and affected devices running versions prior to 3.1.0.1 should be upgraded. CISA notes these issues are not remotely exploitable and recommends updating to 3.1.0.1 and implementing network hardening controls.
read more →